Dux 135DC5P 소유자 매뉴얼 - 페이지 4
{카테고리_이름} Dux 135DC5P에 대한 소유자 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Dux 135DC5P 20 페이지. Gas hot water heaters
Note - all models are equipped
with sacrificial anodes, most are
accessible through the top cover. It is
recommended that a distance of 50% of
the height of the water heater is provided
as clearance above the water heater.
This will assist in the replacement of the
anodes.
Clearances:
Clause 6.9 of AS/NZS 5601.1 specifies
the minimum clearances required
between the water heater and building
features, structures and other items.
As a guide, some of the common
clearance requirements are set out
below:
•
At least 300 mm below any eaves,
balconies or other projections.
Note that at least half the height of
ELECTRICITY METER
OR FUSE BOX
500mm MIN
2
Owner's Manual – Prodigy 4 & 5
Installation Requirements
500mm MIN
the water heater is recommended as
clearance to provide access to the
anode.
•
At least 500 mm from any external
corner.
•
At least 500 mm from any return
wall or other structure facing the
side of the water heater.
•
At least 1000 mm from any gas
meter.
•
At least 500 mm from any electricity
meter or fuse box.
•
At least 500 mm from any openable
window or door.
For a full list of the requirements and
exemptions please refer to
AS/NZS 5601.1.
GAS METER
300mm MIN
1000mm MIN
500mm MIN
500mm MIN
WINDOW OR
OTHER OPENING
DOOR
500mm MIN
H3109
3109
Rev. L