The table below outlines the limitations and
requirements depending on whether you are
using WebCTRL or SuperVision to
communicate with your InterOP8500.
WebCTRL
Module Driver
DRV_InterO
P8500
Number of Function
100
Blocks*
Number of BACnet
2000
Objects*
* depending on available memory
For more information, see the appropriate
module driver document on the Automated
Logic website at www.automatedlogic.com.
U-Line: 9600 bps or 38400 bps
U-Cards
Revised 7/10/01 • InterOP8500
SuperVision
85M
59
1000
MX-Line
CMnet (ARC156)
TNPB
UNI/32
Figure 2. Network Architecture
Specifications
Power 5VDC, 175mA (external), 275 mA
(internal).
12VDC, 25mA.
12VDC, 175mA (external power), 25 mA
(internal power) supplied through the
card-edge connector.
24VAC, 300mA for use with the large
keypad/display.
Inputs 8 binary inputs, 15 analog inputs
(configurable for 1k ohm nickel RTD or 1
to 5V).
Input Resolution 12 bit A/D.
Digital Outputs 16 digital outputs,
12VDC, 300mA fused output.
Communication For WebCTRL, 156 kbps
BACnet-over-ARCNET and 9600 bps or
38.4 kbps EIA-485 BACnet MS/TP.
For SuperVision, 156 kbps BACnet-over-
ARCNET, 9600 bps or 38.4 kbps Legacy
CMnet. Access Port:9600 bps or 38.4 kbps
EIA-485.
For WebCTRL, BACnet/IP.
For SuperVision, BACnet/Ethernet.
LGRM-E
MX-Line
S-Line
Johnson
Field Device
Johnson
Field Device
3
© 2001 Automated Logic Corporation
InterOp8500
Johnson Field
Termination Board
Johnson
Field Device
Johnson
Field Device
Johnson I/O Devices