Automated Logic InterOP8500 Technische instructies - Pagina 3
Blader online of download pdf Technische instructies voor {categorie_naam} Automated Logic InterOP8500. Automated Logic InterOP8500 20 pagina's.
The table below outlines the limitations and
requirements depending on whether you are
using WebCTRL or SuperVision to
communicate with your InterOP8500.
WebCTRL
Module Driver
DRV_InterO
P8500
Number of Function
100
Blocks*
Number of BACnet
2000
Objects*
* depending on available memory
For more information, see the appropriate
module driver document on the Automated
Logic website at www.automatedlogic.com.
U-Line: 9600 bps or 38400 bps
U-Cards
Revised 7/10/01 • InterOP8500
SuperVision
85M
59
1000
MX-Line
CMnet (ARC156)
TNPB
UNI/32
Figure 2. Network Architecture
Specifications
Power 5VDC, 175mA (external), 275 mA
(internal).
12VDC, 25mA.
12VDC, 175mA (external power), 25 mA
(internal power) supplied through the
card-edge connector.
24VAC, 300mA for use with the large
keypad/display.
Inputs 8 binary inputs, 15 analog inputs
(configurable for 1k ohm nickel RTD or 1
to 5V).
Input Resolution 12 bit A/D.
Digital Outputs 16 digital outputs,
12VDC, 300mA fused output.
Communication For WebCTRL, 156 kbps
BACnet-over-ARCNET and 9600 bps or
38.4 kbps EIA-485 BACnet MS/TP.
For SuperVision, 156 kbps BACnet-over-
ARCNET, 9600 bps or 38.4 kbps Legacy
CMnet. Access Port:9600 bps or 38.4 kbps
EIA-485.
For WebCTRL, BACnet/IP.
For SuperVision, BACnet/Ethernet.
LGRM-E
MX-Line
S-Line
Johnson
Field Device
Johnson
Field Device
3
© 2001 Automated Logic Corporation
InterOp8500
Johnson Field
Termination Board
Johnson
Field Device
Johnson
Field Device
Johnson I/O Devices