Automated Logic UNI/16 Instructions techniques - Page 6
Parcourez en ligne ou téléchargez le pdf Instructions techniques pour {nom_de_la_catégorie} Automated Logic UNI/16. Automated Logic UNI/16 8 pages.
type MO
, , module address,15
and press Enter.
3. Transfer memory to the module.
• In SuperVision v3.0, click Tools-
Troubleshooting-Transfer Memory to
Module.
• In SuperVision v2.6b, choose Download
Memory for This Module.
4. When the memory transfer is finished,
check the module status report again.
Make sure the FB List on this page shows
all the FBs you intended to transfer.
Using Flow Sensors
The UNI/16 supports U-Line modules that use
flow sensors. You must calibrate each sensor
to ensure accurate readings. Use the
calibration instructions on the Parameter
page of each FB that uses a flow sensor. You
must indicate on the U1M's Parameter page
(in the U-Card Flow Control section) how air
flow is controlled by each U-Line module.
Refer to the U1M Module Driver document for
details.
Troubleshooting Tips
If you are having trouble communicating with
the UNI/16, check these items before
contacting Technical Support.
• Make sure the U-Line wiring is correct.
In more complex systems, make sure
that all cables involved are attached
correctly.
• Make sure the UNI/16 and the U-Line
modules have power and are turned on.
In more complex systems, make sure all
equipment has power and is turned on.
Some devices, especially
communication devices, receive power
from a source other than a power cable
or adapter (for example, some devices
receive power through communication
Revised 4/27/00 • UNI/16
lines). Some panels can be reinitialized
by resetting the panel.
• Make sure the module driver and all
GFBs are transferred into the module.
You can verify this by checking the
module status page for the UNI/16
module.
• Make sure the module driver
parameters and the parameters for each
GFB are set up properly in SuperVision.
Communicating with the Workstation
You can connect a workstation or portable
computer directly to the UNI/16 module using
an APT and the module's Access port (see
Figure 8). This type of connection can be used
to troubleshoot the module or transfer
memory.
A P T
5
9
6 1
2- Tx out
3- Rx i n
Rx
5- Gnd
1,6,8- +10V or floating
Figure 8. Using the Access Port
The baud rate of the Access port is
determined by the first switch on the eight-
position DIP switch (see Figure 7 on page 5). If
you need to change the switch's position, turn
the UNI/16 module off first. Once you have
adjusted the switch, turn the module back on.
1. Connect the computer's serial port to the
EIA-232 port of the APT using a standard
straight-through serial cable.
2. Set the APT's Mode Select switch.
• On an ARC156 CMnet, use the TTL
setting.
6
© 2000 Automated Logic Corporation
Exec. 4 relay
Isolate Network
ACCESS
PORT
Mode Select
Tx
+5V
TTL
485