9
The Overspeed LED will illuminate when the Engine's speed exceeds the value set by the user unless
Overspeed has been disabled in the software.
LOSS OF SPEED LED: RED
The Loss of Speed LED will illuminate when the speed signal drops to zero while the Engine is running.
LOW BATTERY LED: RED
The Low Battery LED will illuminate when the battery voltage drops below the value set by the user.
ENGINE RUN LED: GREEN
The Engine Run LED will illuminate when the engine starts and speed is detected by the controller.
AUXILIARY LED: RED
The Auxiliary LED has two purposes, first as an indication for Auxiliary Output 1, which can be set for one of
6 different functions by the user, and also as an indication for Auxiliary Output 2, which also can be set for one
of 6 different functions by the user. Both Auxiliary outputs can also be disabled in the software. When the
chosen function of Auxiliary Output 1 goes active the Auxiliary LED will flash as the indication. When the
chosen function of Auxiliary Output 2 goes active the Auxiliary LED will be steady on to indicate the failure.
NORMAL AVAILABLE LED: GREEN
The Normal Available LED will illuminate when the Voltage Sensing detects that the Utility is available.
TRANSFER TO NORMAL LED: GREEN
The Transfer to Normal LED will illuminate when the Transfer Switch is in the Normal position.
EMERGENCY AVAILABLE LED: RED
The Emergency Available LED will illuminate when the Voltage Sensing detects that the Generator source is
available.
TRANSFER TO EMERGENCY LED: RED
The Transfer to Emergency LED will illuminate when the Transfer Switch is in the Emergency position.
LCD DISPLAY:
The LCD display will show the total time that the generator has ran. This time is displayed when the controller
is in Engine run mode and can not be reset.