DynaGen GSC200 Посібник з встановлення та експлуатації - Сторінка 10

Переглянути онлайн або завантажити pdf Посібник з встановлення та експлуатації для Контролер DynaGen GSC200. DynaGen GSC200 11 сторінок. Auto start engine & transfer switch controller

9
The Overspeed LED will illuminate when the Engine's speed exceeds the value set by the user unless
Overspeed has been disabled in the software.
LOSS OF SPEED LED: RED
The Loss of Speed LED will illuminate when the speed signal drops to zero while the Engine is running.
LOW BATTERY LED: RED
The Low Battery LED will illuminate when the battery voltage drops below the value set by the user.
ENGINE RUN LED: GREEN
The Engine Run LED will illuminate when the engine starts and speed is detected by the controller.
AUXILIARY LED: RED
The Auxiliary LED has two purposes, first as an indication for Auxiliary Output 1, which can be set for one of
6 different functions by the user, and also as an indication for Auxiliary Output 2, which also can be set for one
of 6 different functions by the user. Both Auxiliary outputs can also be disabled in the software. When the
chosen function of Auxiliary Output 1 goes active the Auxiliary LED will flash as the indication. When the
chosen function of Auxiliary Output 2 goes active the Auxiliary LED will be steady on to indicate the failure.
NORMAL AVAILABLE LED: GREEN
The Normal Available LED will illuminate when the Voltage Sensing detects that the Utility is available.
TRANSFER TO NORMAL LED: GREEN
The Transfer to Normal LED will illuminate when the Transfer Switch is in the Normal position.
EMERGENCY AVAILABLE LED: RED
The Emergency Available LED will illuminate when the Voltage Sensing detects that the Generator source is
available.
TRANSFER TO EMERGENCY LED: RED
The Transfer to Emergency LED will illuminate when the Transfer Switch is in the Emergency position.
LCD DISPLAY:
The LCD display will show the total time that the generator has ran. This time is displayed when the controller
is in Engine run mode and can not be reset.
Operating & Installation Manual for the GSC200 Controller