Automationdirect.com DURApulse GS10 Manuel de démarrage rapide - Page 3

Parcourez en ligne ou téléchargez le pdf Manuel de démarrage rapide pour {nom_de_la_catégorie} Automationdirect.com DURApulse GS10. Automationdirect.com DURApulse GS10 5 pages.

Automationdirect.com DURApulse GS10 Manuel de démarrage rapide
DURApulse GS10 AC Drive Quick-Start Guide
Digital Keypad Functions and Indications
Description of the functions of the keys and indicators of the GS10 AC Drive Keypad.
NOTE: Drive default is AUTO mode. There is no indication from the keypad of the mode.
Local mode can be set with I/O configuration or GS4-KPD only.
Descriptions of Keypad Functions
RUN Key
• Valid only when the source of operation command is from the keypad.
• RUN can be pressed even when drive is in process of stopping.
• When in "LOCAL" mode, RUN is valid only when the source of operation command is from the keypad (drive default is Auto mode, Local
mode can be set with I/O or GS4-KPD only).
STOP/RESET Key
This key has the highest processing priority in any situation.
• When the drive receives a STOP command, whether or not the drive is in operation or stop status, the drive will execute a "STOP"
command.
• The RESET key can be used to reset the drive after a fault occurs. For those faults that can't be reset by the RESET key, see the fault records
after pressing MENU key for details.
N OTE: The ability to STOP the drive from the keypad is effective ONLY if the drive is configured to RUN and/or STOP from the keypad. Keypad
STOP can be disabled by parameter 00.32, Digital Keypad STOP Function.
ENTER Key
Press ENTER to go to the next menu level or accept parameter entry. If it is the last level, then press ENTER to execute the command.
MENU Key
Press MENU to return to the Main Menu or cycle through the available menu options.
Direction: Up
Press to make the value set on the current menu/parameter higher.
Direction: Left/Down
• Press to make the value set on the current menu/parameter lower.
• In the menu/text selection mode, the arrows are used for item selection. Long press the MENU key to use the left direction function.
Frequency Setting Dial (Potentiometer)
The dial can be set as the main frequency input. Set Parameter 00-20 or 00-30 to '7-Digital Keypad Dial'.
Descriptions of LED Functions
Steady ON: Drive is running.
Blinking: Drive is stopping or in base block.
RUN
Steady OFF: Drive is not running.
Steady ON: Drive is operating in Forward mode.
Blinking: Drive is changing direction.
FWD
Steady OFF: Drive is operating in Reverse mode.
Steady ON: Drive is operating in Reverse mode.
Blinking: Drive is changing direction.
REV
Steady OFF: Drive is operating in Forward mode.
Steady ON: Drive is stopped or in the process of stopping.
Blinking: Drive is in standby (run but does not output).
Steady OFF: Drive is not currently executing an operational (STOP) command.
STOP
N OTE: The ability to STOP the drive from the keypad is effective ONLY if the drive is configured to RUN and/or STOP from the keypad.
Keypad STOP can be disabled by parameter 00.32, Digital Keypad STOP Function.
GS10_QSP 1st Edition 06/15/2022
Keypad Navigation Example
Instruction
First menu to display after power up.
Press MENU once from startup.
Press MENU twice from startup.
Press MENU three times from startup.
Press MENU four times from startup. Displays Frd if the drive is currently
configured for Forward operation. Press the UP or DOWN key to change to
Reverse. Press ENTER to confirm the change.
Enable the counter by setting parameter 00.04 to 1. See the user manual for
full instructions on using the counter.
After selecting the desired menu option, press ENTER to bring up the
parameter number (Format XX.YY). Use the UP and DOWN arrow keys to
change the parameter number as needed, then press ENTER to adjust the
parameter value.
From the parameter number screen, press ENTER to bring up the current
value of the selected parameter. Use the UP and DOWN arrows to adjust
the value. Press ENTER again to confirm the choice.
Once a desired parameter value has been set using the UP and DOWN arrow
keys, press ENTER to save the choice and display End message.
Displays when an external fault is detected.
Displays when data is not accepted or the value exceeded.
After changing all of the applicable parameters, press MENU key to return to the Menu screen, and then press ESC key to return to the home screen.
GS10 Fault Codes
See Chapter 6 of the User Manual for more details.
Number
Code
Description
0
n/a
No Error
1
ocA
Overcurrent during Accel
2
ocd
Overcurrent during Decel
3
ocn
Overcurrent during constant speed
4
GFF
Ground Fault
6
ocS
Overcurrent during Stop
7
ovA
Overvoltage during Accel
8
ovd
Overvoltage during Decel
9
ovn
Overvoltage during constant speed
10
ovS
Overvoltage during Stop
11
LvA
Low voltage during Accel
12
Lvd
Low voltage during Decel
13
Lvn
Low voltage during constant speed
14
LvS
Low voltage during Stop
15
OrP
Input phase loss
16
oH1
IGBT Overheat 1
18
tH1o
Thermister 1 open
21
oL
Drive overload
22
EoL1
Electronics thermal relay protection 1
23
EoL2
Electronics thermal relay protection 2
24
oH3
Motor Overheat-PTC
26
ot1
Over Torque 1
27
ot2
Over Torque 2
28
uc
Under current
31
cF2
Memory read-out error
33
cd1
U phase current sensor detection error
34
cd2
V phase current sensor detection error
35
cd3
W phase current sensor detection error
36
Hd0
Clamp current detection error
Press Key
Display Will Show
Displays the present
n/a
frequency setting of the
drive
Displays the actual output
MENU
frequency of the drive
Displays user defined
MENU
output
MENU
Displays output current
Displays the Forward
command if configured for
MENU,
Forward operation
UP/DOWN
Displays the Reverse
ENTER
command if configured for
Reverse operation
MENU
Displays the counter value
ENTER, UP/
Displays the parameter
DOWN,
number
ENTER
ENTER, UP/
Displays the value of the
DOWN
selected parameter
End message. Displays when
ENTER
data has been accepted and
stored
n/a
External fault message
n/a
Error message
Fault Codes
Number
Code
Description
37
Hd1
Over-current detection error
40
AuE
Auto tuning error
41
AFE
PID Feedback loss
48
ACE
Analog current input loss
49
EF
External Fault input
50
EF1
Emergency Stop
51
bb
External Base Block
52
Pcod
Password Error
54
CE1
Communication Error
55
CE2
Communication Error
56
CE3
Communication Error
57
CE4
Communication Error
58
CE10
PC Communication Time Out
61
ydc
Y-Delta connection Error
62
dEb
Decel Energy Backup Error
63
oSL
Slip Error
79
Aoc
U Phase over current before run
80
boc
V Phase over current before run
81
coc
W Phase over current before run
72
oPL1
U Phase output phase loss
73
oPL2
V Phase output phase loss
84
oPL3
W Phase output phase loss
87
oL3
Drive over load in low frequency
89
roPd
Initial rotor position detection error
140
Hd6
GFF detected when power on
141
b4GFF
GFF occurs before run
142
AUE1
Auto tuning error 1 (DC test stage)
143
AUE2
Auto tuning error 2 (High frequency test stage)
144
AUE3
Auto tuning error 3 (Rotary test stage)
GS10 AC Drive Quick-Start Guide – 1st Ed 06/15/2022
Page 3