AGS Merlin WTM Instructions d'installation et d'utilisation - Page 6
Parcourez en ligne ou téléchargez le pdf Instructions d'installation et d'utilisation pour {nom_de_la_catégorie} AGS Merlin WTM. AGS Merlin WTM 10 pages. Water temperature monitor
AGS WTM Installation, Operation & Maintenance
Valve Outputs
Use grounding terminals for gas valves not considered class II apparatus!
Connecting two valves to both mains 120V~ and 24V~ simultaneously is considered misuse – use only one
valve output!
A water solenoid valve should be powered using one of the terminals marked [VALVE OUT].
Terminals offer control via 100-120V~ or 24V~. When wired to a normally closed water solenoid valve, the
WTM controller can be used to isolate the water supply when water temperature is outside of allowable Max
and Min temperature settings.
BMS Relay Output
Connections are available on the board for Building Management Systems. [NO - Normally Open] [C -
Common] [NC - Normally Closed]. This is a relay that changes state in alarm / water off.
0-10V Analog Output
A single 0-10V output is scaled to the PT100 temperature sensor as follows.
32°F
50°F
68°F
86°F
104°F
122°F
140°F
158°F
176°F
194°F
212°F
0V
1V
2V
3V
4V
5V
6V
7V
8V
9V
10V
PT100 Temperature Sensor Input
Adjust Min and Max Allowable Water Temperature
Turn On the dipswitch [SET] located on the circuit board to program Min and Max water temperature.
Using Up and Down arrows located on the front fascia select required Min temperature.
Press OK and repeat for Max temperature. Turn Off the dipswitch [SET] to exit temperature
programming menu and save.