Fan Switch Integration

There is the facility to connect a Fan Switch (FS1 or FS2 sold
separately).
The Fan Switch provides the facility to turn the fan(s) ON when the
Merlin panel is on and turn the fans OFF when the panel is
switched off
There is a dip-switch located inside the facia of the Merlin 1000S
labelled [EM SELECTION].
This is factory set in the 'OFF' position which instructs the system to
shut down the fan(s) and gas supply on activation of the
Emergency shut off button(s).
On installation, this can be switched to the 'ON' position, this will instruct the system to leave
the fans on and only shut off the gas supply on activation of an Emergency shut off button.
Note: This option is not available if a Fan Switch is not installed.
Gas Fill & Prove Time
Gas fill and prove times are adjustable. There are two dip-switches
located on the inside facia of the Merlin 1000S labelled [FILL TIME]
and [PROVE TIME].
They are factory set in the OFF position.
Fill and prove time can be changed by switching the relevant dip
switch as follows;
[FILL TIME]: Off – 5 seconds.
[PROVE TIME] Off – 30 seconds.
Once selected - please remove power from the fuse spur for 10 seconds.

Auto-Reset

The Merlin 1000S has a built-in auto reset feature. There is a dip-
switch located on the inside facia of the Merlin 1000S labelled
[Auto Reset].
This is factory set in the 'OFF' position, this means, if you experience
a power cut, the panel has to be restarted manually.
This can be switched to the 'ON' position and will instruct the
system to restart automatically when power is restored following a
power cut or similar situation.