Flue Connections and Outlets
Dean Stoves can be flued from the top and the back, or with a vertical back box. Horizontal
flue from back of stove should not exceed 150mm.
All flue connections must be sealed. Doors in the register plate must be present or a soot box
fitted in the back or side of the fireplace to enable access to clean the chimney when the stove
is installed without a flue liner.
If the chimney has been lined and cannot be swept through the stove an access door on the first
length of flue must be installed for cleaning access.
The Hembury 5 SE model requires a 125mm (5") first length of flue then stepping up into a
minimum of 150mm (6") liner. When the Hembury 5 SE has a smoke except air slider fitted
the flue liner can be reduced to 125mm (5"). We strongly advise a 150mm (6") flue liner be
fitted when possible.
Diagrams showing the flue outlet from the top (A), back (B) and back box (C).
X = Position of baffle plat
Y = Back protection brick
Please Note: All Profile top stoves use the 6mm black rope seal supplied under the flue spigot
to bring the flue spigot flush with the stove
9