Gree FLEXX36C Manuel d'installation - Page 8
Parcourez en ligne ou téléchargez le pdf Manuel d'installation pour {nom_de_la_catégorie} Gree FLEXX36C. Gree FLEXX36C 19 pages. A coils
A-Coil
2.5 General Information
Cooling capacity range as shown below:
Model
FLEXX24C
FLEXX36C
FLEXX48C
FLEXX60C
3 General
The evaporator of indoor unit is charged with refrigerant in factory for pressure
maintaining. The cut-off valve can be opened only when installation and vacuuming is
done.
The drain pan must be at least 2" away from a standard gas-fired furnace heat
exchanger and at least 4"-6" away from any drum-type or oil-fired furnace heat
exchanger, depending on furnace model. Closer spacing may damage the drain pan
and cause a leak.
Refer to the Product Specification for the proper use of these coils with specific
furnaces, air handlers, condensers and line sets.
4 Installation
4.1 Pre-Installation Instruction
4.1.1 Checking Product Received
After receiving the product, please check if there is any damage caused by
transportation. Shipping damage is the responsibility of the carrier. Verify the model
number, specifications and accessories are correct prior to installation. The distributor
or manufacturer will not accept claims from dealers for transportation damage or
installation of incorrectly shipped units.
4.1.2 Before Installation
Carefully read all instructions for the installation prior to installing product. Make
sure each step or procedure is understood and any special considerations are taken
into account before starting installation. Assemble all tools, hardware and supplies
needed to complete the installation. Some items may need to be purchased locally.
Make sure everything needed to install the product is on hand before starting.
Cooling capacity(ton)
4
2.0
3.0
4.0
5.0