Testing Generator Output at Main Circuit Breaker
( ​ c ontinued from the previous page ​ ) .
WARNING: Dangerous voltage and/or current may be present when a
voltage test is being conducted. To reduce risk of serious injury or death from electrical
shock, if you are not trained to safely work with high voltage, do not attempt any of these
procedures. You must seek assistance from qualified personnel.
If the previous procedure indicates proper voltage at the top (Input) main breaker
terminals ( see figure M.1 and A.1 on the next page). The meter reading should indicate
120 volts +10%. If a reading of 120 volts +10% is not measured at each terminal, the
main breaker is faulty and must be replaced. See page 1 for a list of parts, visit our web
site at ​
w ww.allmand.com/support/productsmanualsliterature.aspx​
breakdowns, or contact the Allmand parts and service team at 1- 800-562-1373 for
correct replacement circuit breakers.
Figure M.1
MAXI LITE II 
for a full list of parts