FLUIDIC CONNECTION

Possible expansion steps
• 24 V DC, 24 V AC, 110 / 230 V UC without communication
• AS interface
• DeviceNet
• Inductive proximity switches or
• Mechanical limit switches (microswitches): only in
connection with UC without communication
Various pneumatically operated process valves can be
combined with the Control Head Type 1066 to suit different
conditions of use. Single-acting and double-acting valves are
suitable; a third position (an intermediate position on use of a
third initiator) can be moved to. Mounting on the process valve
is done with a suitable flange adapter (see Operating
Instructions for Type 1066).
Connection of the control air
Compressed
air
(G 1/4)
Valves V1, V2, V3
(plug connectors for hose 6/4 or 1/4")
Installation of the valve
• Assemble the process valve according to manufacturer's
instructions.
• For mounting the control head on the process valve, a valve-
specific flange adapter is required.
(see Operating Instructions for Type 1066)
• Installation of control head in any orientation but preferably
upright.
GB

ELECTRICAL CONNECTION

Control heads without communication
Printed card for 24 V DC
Status indication of valves V1, V2 and V3 by LED
24 V DC version 1
Direct connection to 8-pole screw terminal on the printed card;
for this purpose, be sure to remove the control head cover.
Exhaust
air
(G 1/4)
24 V DC version 2
Connection via 8-pole circular connector to DIN 45326; the
internal connections to the screw terminal are already executed.
GB
Control heads without communication
24 / 110 / 230 V UC
Connection via 2x6-pole screw terminals; each allocated to a
valve Type 6102; 2 mechanical micro limit switches; no LED
status display.
Printed card for 24 / 110 / 230 V UC
Adjustments during commissioning
To adjust the proximity switches or limit switches:
- remove control head
- adjust proximity
1 Valve 2
2 +24 DC for proximity switches
- replace cover
3 proximity switch 2
4 Valve 1
5 proximity switch 1
6 Valve 3
7 proximity switch 3
8 GND (common mass)
ELECTRICAL CONNECTION
switches via
setscrews
(for adjustment,
see Operating
Instructions)
GB
Adjusting screws
(spindles) for
proximity switches
Turn clockwise:
proximity switch
moves upwards
Turn anticlockwise:
proximity switch
moves downwards