Accutrol AFM5000 Manuel de démarrage rapide - Page 2

Parcourez en ligne ou téléchargez le pdf Manuel de démarrage rapide pour {nom_de_la_catégorie} Accutrol AFM5000. Accutrol AFM5000 2 pages. Air flow monitor for controller covers

 
Remove the rubber port plug
to access the AFM5000 USB
Port.
Plug USB Mini Cable from PC into
the AFM5000 USB Port.
Connect PC to AFM5000
Open the AVC Insight
UI Program.
(Jumper position)
In
the
MODE OF
OPERATION window above:

coming from AI-1, Dry Contact, or BACnet Communications.

If ANALOG (AI-1), Select Analog signal (be sure to
configure input at AVC5000 by moving JP-3 as described).

For AFM5001, ANALOG AI-1 is set up for Resistor (R)

Select the range of the set point signal in the bottom
window.
Verify
Mode
Operation is SETPOINT
MODE
Select whether the set point is

With the OVERRIDE
button,
MANUAL and a value
in % to force the
the
actuator to a specific
of
position,
(the
face will go red).

Go to OVERRIDE and select AUTO to release control, (the
gage face will go back to normal).
In the TUNING window above:

Adjust the Deadband%, Gain (P) and the
Integral (I) to address tuning.

Adjust the OFFSET or differential in a
tracking valve application
In the ALARM window above:

Enable and Disable Alarms

Select Airflow Volume Alarm or Set Point Deviation
Alarm

Enter values and delays
In the A0-1 and AO-2 Window on the right:

Configure the AO Signals to Voltage or Current

Set either for Volume or Output position

Manually operate the Outputs to a value for trouble shooting
In the CONTROL OUTPUT window
above:
Select
gage