Accutrol AFM5000 빠른 시작 매뉴얼 - 페이지 2
{카테고리_이름} Accutrol AFM5000에 대한 빠른 시작 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Accutrol AFM5000 2 페이지. Air flow monitor for controller covers
Remove the rubber port plug
to access the AFM5000 USB
Port.
Plug USB Mini Cable from PC into
the AFM5000 USB Port.
Connect PC to AFM5000
Open the AVC Insight
UI Program.
(Jumper position)
In
the
MODE OF
OPERATION window above:
coming from AI-1, Dry Contact, or BACnet Communications.
If ANALOG (AI-1), Select Analog signal (be sure to
configure input at AVC5000 by moving JP-3 as described).
For AFM5001, ANALOG AI-1 is set up for Resistor (R)
Select the range of the set point signal in the bottom
window.
Verify
Mode
Operation is SETPOINT
MODE
Select whether the set point is
With the OVERRIDE
button,
MANUAL and a value
in % to force the
the
actuator to a specific
of
position,
(the
face will go red).
Go to OVERRIDE and select AUTO to release control, (the
gage face will go back to normal).
In the TUNING window above:
Adjust the Deadband%, Gain (P) and the
Integral (I) to address tuning.
Adjust the OFFSET or differential in a
tracking valve application
In the ALARM window above:
Enable and Disable Alarms
Select Airflow Volume Alarm or Set Point Deviation
Alarm
Enter values and delays
In the A0-1 and AO-2 Window on the right:
Configure the AO Signals to Voltage or Current
Set either for Volume or Output position
Manually operate the Outputs to a value for trouble shooting
2
In the CONTROL OUTPUT window
above:
Select
gage