Connecting Power

The RUGGEDCOM RS1600 supports single or dual redundant high AC, high DC and/or
low DC power supplies. The use of two power modules is recommended to provide
redundancy and load balancing.
The RUGGEDCOM RS1600 can be equipped with either a screw-type or pluggable
terminal block, which provides power to both power supplies. The screw-type
terminal block is installed using Philips screws and compression plates, allowing
either bare wire connections or crimped terminal lugs. Use #6 size ring lugs for
secure, reliable connections under severe shock or vibration.
RUGGEDCOM RS1600
Installation Manual, 11/2022, C79000-G8976-1013-04
1
1
Screw
1
Panel/DIN Rail Adapter
2
Figure 2.3
Panel Mounting
Install the supplied screws to secure the adapters to the panel.
NOTICE
For maximum redundancy in a dual power supply configuration, use two
independent power sources.
For 100-240 VAC rated equipment, an appropriately rated AC circuit breaker
must be installed.
For 88-300 VDC rated equipment, an appropriately rated DC circuit breaker must
be installed.