a. The doors should start moving and the DRIVE and MOTOR reading in the
DIAGNOSTICS menu should increase. If the doors do not move refer to section ??????
b. When the doors are fully open the DRIVE and MOTOR readings should go to 0 and the
OL LED should light
6. Set the OPEN/CLOSE switch to the CLOSE position.
a.
The doors should start moving in the CLOSE direction and the MOTOR and DRIVE
readings should increase. If the doors do not move refer to section ????
b. When the doors are fully closed the MOTOR and DRIVE readings should go to 0 and the
CL LED should light.

8.2 Door Adjustments

8.2.1 Adjustment Notes

This equipment is to be installed, adjusted and maintained to conform to code requirements. Parameters
must be set to conform to kinetic energy code limitations for both maximum and average kinetic energy
for ALL doors/all floors (specialty or otherwise heavy doors taken into account).
Parameters must be set to conform to closing force limitations. The closing force may not exceed 135N
(30lbs). During the closing, the kinetic energy may not exceed 10 joules (7.4lb/ft)

8.2.2 Door Speed Adjustments

Select the EDIT PARAMETERs menu
At this time adjustments can be made to open and close speeds by moving the cursor to the desired setting
and pressing the ENTER button. Any changes happen in real time so there is no need to press enter for
each change. When complete press the ENTER button and move to the next parameter. Refer to Figure 4
for an example of OPEN and CLOSE cycles.
To adjust NUDGING set the NUDGE/LOCK switch to the NUDGE position then set the OPEN/CLOSE
switch to CLOSE.
To adjust DOOR LOCKING FORCE (DLF) have the door fully closed. Set the NUDGE/LOCK switch
to LOCK then set the OPEN/CLOSE switch to the CLOSE position.

8.2.3 Heavy Door Adjustment

1. Heavy door adjustments must be made at a heavy door entrance.
2. Check that there is 24VDC at connector X7 pins HDP and HDN.
3. Starting from a fully open position, TEST/RUN switch in TEST, set the OPEN/CLOSE switch to
CLOSE and adjust the CFH (Close Fast Heavy door) parameter. Adjust the HDCSDL cam for
smooth operation if required.