Toshiba BMS-IFMB0TLR-E Manuel d'installation - Page 3
Parcourez en ligne ou téléchargez le pdf Manuel d'installation pour {nom_de_la_catégorie} Toshiba BMS-IFMB0TLR-E. Toshiba BMS-IFMB0TLR-E 4 pages. Mb interface
MB Interface
Configuration through micro switches
L1 L2 S1
A
B
TOSHIBA
BMS-IFMB0TLR-E
RS-485
A+
B-
S3
S4
S1 - MB Interface Setting
Switches
1 2 3 4
x x x
x x x
x x x
x x x
x x x
S3 - Modbus slave address and baudrate
Switches
Switches
Add
Add
1 2 3 4 5 6
1 2 3 4 5 6
0
8
1*
9
2
10
3
11
4
12
5
13
6
14
7
15
* Default value
Switches
7 8
S4 - Degrees/Decidegrees (x10), temperature magnitude (ºC) and RS-485 termination resistor
Switches
1 2 3 4
x x x
x x x
x x x
x x x
* Only in the interfaces conected at both ends of the bus must be activated the termination resistor, not in the rest. The RS-485 bus can be biased through internal
jumpers JP2 and JP3. Consult the user manual for details.
WEEE Document and e-waste document for India
http://www.toshiba-carrier.co.jp/global/products/network/index.htm
S1
MB Interface Setting. This setting depend on Remote Controller connection.
ON 1 2 3 4
Please check Remote Controller connect or not.
Normal operation: At device start-up, both LEDs are on during 5 seconds.
L1 (green)
Afterwards only the green LED remains flashing (1900ms Off/100ms On). For
L2 (red)
any other indication, consult the User Manual.
Modbus slave address and Baudrate
configuration.
Configuration degrees/decidegrees (x10),
ON 1 2 3 4 5 6 7 8
ON 1 2 3 4
temperature magnitude (ºC) and RS- 485
termination resistor.
S3
S4
Connet Wired Remote Controller and/or Wireless Remote Controller (default setting)
Not Connet Wired Remote Controller and Wireless Remote Controller.
Reserve.
Reserve.
Reserve.
Switches
Switches
Add
Add
1 2 3 4 5 6
1 2 3 4 5 6
16
24
17
25
18
26
19
27
20
28
21
29
22
30
23
31
2400bps
4800bps
9600bps (default value)
19200bps
Temperature values in Modbus register are represented in degrees (x1) (default value)
Temperature values in Modbus register are represented in decidegrees (x10)
RS-485 bus without termination resistor (default value)
Internal termination resistor of 120Ω connected to RS-485 bus *
Description
Switches
Switches
Add
Add
1 2 3 4 5 6
1 2 3 4 5 6
32
40
33
41
34
42
35
43
36
44
37
45
38
46
39
47
Description
Description
Installation Manual
Switches
Switches
Add
Add
1 2 3 4 5 6
1 2 3 4 5 6
48
56
49
57
50
58
51
59
52
60
53
61
54
62
55
63
3
-EN