ABB FPBA-01 PROFIBUS DP Manuel d'installation et de démarrage rapide - Page 2
Parcourez en ligne ou téléchargez le pdf Manuel d'installation et de démarrage rapide pour {nom_de_la_catégorie} ABB FPBA-01 PROFIBUS DP. ABB FPBA-01 PROFIBUS DP 2 pages. Profibus dp adapter module
Également pour ABB FPBA-01 PROFIBUS DP : Manuel d'installation et de démarrage rapide (2 pages)
Connection procedure
ABB recommends that you use a PROFIBUS-
approved D-SUB 9 connector. These
connectors have a built-in termination
network and inductors for station
capacitance compensation.
Connect the cable to the D-SUB connector as
shown in the figure.
Start-up
To control the drive with the adapter module, set at least the basic parameters listed in the table
below. For full parameter descriptions, refer to the adapter module's user manual or to the drive's
firmware manual.
Basic parameter settings
Index
Name
20.01
Ext1 commands
22.11
Speed ref1 source
28.11
Frequency ref1 source FBA A ref 1
50.01
FBA A enable
50.02
FBA A comm loss func Fault
51.02
Node address
51.05
Profile
52.01
FBA A data in1
52.02
FBA A data in2
53.01
FBA A data out1
53.02
FBA A data out2
To take the settings into use, validate and refresh the parameters with parameter 51.27 FBA par
refresh.
Further information
See the latest version of FPBA-01 PROFIBUS DP adapter module
user's manual (3AFE68573271 [English]) in ABB library
(www.abb.com/drives/documents).
FPBA-01 manual
abb.com/drives
© Copyright 2023 ABB. All rights reserved.
Specifications subject to change without notice.
Value
Fieldbus A
FBA A ref 1
Enable (or select the option slot in which the module is installed).
Set the node address of the module according to the network
configuration.
The ABB Drives communication profile is the default value.
SW 16bit
Act 16bit
CW 16bit
Ref1 16bit
For more information on ABB fieldbus options and protocols,
see the fieldbus communications web page
(new.abb.com/drives/connectivity/fieldbus-connectivity).
1A
1B
2A
2B
OUT
IN
Fieldbus communications web page
Grounding clamp/
Strain relief