Cabling Requirements
3.6
Cable Requirements - All cabling in the FirePro Installation
MUST be done using 0.75mm shielded Fire Rated Cable. Care
taken to ensure that all cables are isolated, and that RF
shielding on cable is stripped back to ensure that there is not
accidental grounding.
identification.
Extension Leads - Deutsch Plugs must be used to ensure
water-proof connections are made throughout the installation.
Installation of FirePro Generators
4
FirePro Condensed Aerosol Fire Extinguishing System Arrangement.
•
FirePro units and system components installed to allow inspection and maintenance.
•
Locate FirePro units where they are not exposed to mechanical damage, exposed to
chemicals, or weather conditions, that may render them inoperative. Protective provisions
shall be adopted, if necessary.
•
FirePro units shall be securely installed. Use heavy duty brackets where necessary.
Brackets should be capable of handling the risk environment, including vibration.
FirePro units must be installed at NOT less than the minimum safe distances as
specified in the design calculations.
Means for prompt rescue of any trapped personnel shall be provided, including:
•
Adequate aisle ways/routes of exit.
•
Alarms – audible and visual, that operate immediately on detection of the fire.
•
Signs in accordance with relevant standards for the installation.
System components shall be positioned to the minimum clearances from energized electrical
parts as per: AS 4487 and AS 3000.
Handling and Storage - when handling the Condensed Aerosol Generators do not:
•
Disassemble the unit
•
Carry out any welding work in the vicinity of the fire
extinguishing system components.
STORAGE and OPERATIONAL CONDITIONS
•
Temperature: –54 and +54°C
•
Service life: 15 years (date of manufacture appears on each generator)
Cables are colour coded for easy
In Addition to Color Coding the back of the panel is
Marked as shown.
Control Panel
Model 08100
Colour
•
Exert force or impact which creates physical or
mechanical damage to the casing.
•
Humidity: maximum 98% RH
Rev 4.0
Circuit
Red
Power
Yellow
Activation
Green
Detection
Orange
Sounder
Page | 5