Design Considerations
3
Main Power Supply Input
3.1
The FP-08800 Fire Control Panel provide a single power supply input that is compatible with 12
/ 24vDC. If adequate power is not supplied, the power LED will not be illuminated.
Siren/Strobe Output
3.2
When a fire is detected by the LHD cable (if Installed), the internal siren in the FIP will sound
and the RED fire indicator light will flash, and the external siren (if installed) will sound. The
internal and external sirens will also sound whenever the fire system activation occurs.
Discharge Output
3.3
The maximum number of FirePro generators able to be discharged by the FP-08800 Fire Control
Panel is limited by the voltage of the main power supply. That is:
Voltage 12vDC
If a risk area requires a greater number of FirePro generators, the Discharge Delay module
must be used. The module will discharge generators in multiples up to the maximum as above.
If the number of FirePro generators connected to each output is greater than the
maximum, the fire system will not operate.
When multiple FirePro generators are connected to a single output, they must be connected
using the FP-08919 Splitter Lead.
Detection Circuit
3.4
The detection circuit can support Linear Heat Detection Cable. When a fire is detected by the
LHD cable (if Installed), the siren in the FIP will sound and the RED fire indicator light will flash.
To activate the Fire System lift the cover for the switch and push the toggle switch. The siren
will stop once the activation switch has been pushed and the fire indicator light will stay
illumated.
Mounting
3.5
The panel is to be mounted vertically by means of two bolts or screw through
the mounting holes in the flange on the outside of the FIP, as shown below.
No penetrations are to be made through the casing of the panel, except for
cable entry. It may be necessary to complete all wiring and any programming
of the detection mode prior to mounting the FIP.
Max = 2 Units
Voltage 24vDC
Max = 4 Units
Control Panel
Model 08100
Rev 4.0
Page | 4