The FirePro FP-08450 Fire Control Panel is a combined detection and extinguishant system.
The FIP (fire indicator panel) incorporates:
-
1x Non Monitored Detection circuit using Linear Heat Detection Cable;
-
1x Non Monitored Extinguishing Discharge circuit;
-
1x Non Monitored Siren/Strobe circuit;
-
FirePro Monitor Indicators -
Power ON light iluminated – system okay and ready for activation.
o
FIRE Red light – Fire Alarm.
o
All FirePro Fire Extinguishing Aerosol Generators use the latest generation FPC solid compound.
Upon activation, the solid compound is transformed into a rapidly expanding, highly efficient gas,
based on Potassium salts. It does not deplete oxygen levels. Its built-in fail-safe activation system
ensures operation of the generators when required, even if everything else fails. The FirePro
Aerosol Generators have a certified life of 15 years, with minimal maintenance required.
Ozone Depletion Potential (O.D.P.) = 0
Global Warming Potential (G.W.P.) = 0
In Case of Fire
If a fire occurs, equipment operators should do the following:
1.
Detection will initiate an alarm condition on the FirePro System
2.
Evacuate all personnel from the risk area.
3.
Close all hatches and openings, and shutdown engines and any extraction fans or vents.
4.
Manual actuation is from Panel via switch. The Actuate Switch has a Protective cover to
prevent accidental activation. To activate the system flip open the Protective switch cover
and push the spring loaded toggle switch.
5.
When pressed then the manual release switch will immediately ACTIVATE the Fire System.
It will also activate the alarm(s) and the Fire LED will flash.
6.
Keep the FirePro suppression gas within the risk until the fire is extinguished and not able
to re-ignite.
7.
Do not start engine or fans until the fire is extinguished. Operating the exhaust fans will
enable the gas to escape the risk area and could allow the fire to re-ignite.
8.
Do not enter the risk until it has been rendered safe.
9.
Recommended clean up after discharge is with soapy water or cleaning agent based on
citric acid.
Following a discharge, replace all installed FirePro Generators.
10.
This is a MANUALLY ACTIVATED SYSTEM
How Does it Work
Control Panel
Model 08100
Atmospheric Life Time (A.L.T.) = 0
Non-corrosive & Non-toxic