FirePro 08879 Manuel de démarrage rapide - Page 3
Parcourez en ligne ou téléchargez le pdf Manuel de démarrage rapide pour {nom_de_la_catégorie} FirePro 08879. FirePro 08879 4 pages. Digital voltage sensitive relay
operational until the backup battery is depleted.
Note that FirePro systems have a failsafe, the FirePro Generator will self-activate once the
temperature reaches 300ºC.
Cabling Requirements
3.5
The cables are marked RED on the module, and
the plugs are setup Male/Female to ensure
correct installation.
Cables are colour coded for easy identification.
When installing system, cables should be only
connected to the correctly coded cable.
Installation
4
1. Ensure fire control panel is not in an alarm/fault condition.
2. The machine MUST NOT be running.
3. Unplug the Power supply to the FIP.
4. Unplug the FP-14016 Battery Lead from Battery Pack and plug into FP-08879 DVSR. The
DVSR requires a minimum of 5 seconds to allow sampling of the incoming power supply,
to determine operating voltage. This will be indicted by flashing of the LED indicator. When
sampling is complete the LED indicator will stop flashing and remain illuminated.
5. Connect the FP-08879 to a compatible Power Control Module (FP-08872/08873). The
"Charging" LED indicator will illuminate on the Power Control Module connected correctly.
6. It is now safe to connect the power supply to the FIP.
Digital Voltage Sensitive Relay
Model 08879
Colour
Circuit
Red 1
Power Supply
Red 2
Backup Batteries
Yellow 1
Activation
Yellow 2
Activation Delayed
Green 1
Detection 1
Green 2
Detection 2
Blue
Discharge Advice
Orange
Siren/Strobe
White
Relay Output
Rev 1.0