Operation
5
The FP-08879 DVSR operates when the unit is installed and the Main power is active. Should
the main supply fail or drop below operating volatage, the module automatically cuts off the
primary power supply. When the primary supply has been connected the LED will illuminate
to indicate that the primary power supply is available.
When the primary supply has failed or dropped below operating volatage will flash once every
5 seconds to indicate that the primary power supply is being cut off.
If the primary power supply voltage is too high, the DVSR will flash rapidly.
Commissioning
6
Commissioning should be performed after installation.
1. Ensure fire control panel is not in an alarm/fault condition.
2. Run the machine, this should allow full power to the FIP.
3. TURN OFF machine and the Lower voltage will automatically disconnect primary power
supply (depending on state of main machine battery voltage) and ensure LED indicator
begins flashing.
4. Ensure power supply to FIP automatically switches to the backup batteries. This will be
indicated by the LED on the installed Power Control Module switching off, and the FIP
should remain operational.
5. Ensure fire control panel remains operational and out of fault condition.
Servicing and Maintenance
7
Inspection and servicing of the installed fire system should occur in accordance with the
relevant Australian Standards. Monitoring and operation of any installed modules should be
tested as outlined in 6. Commissioning.
Troubleshooting
8
Problem
LED not illuminating
LED flashing rapidly
Specifications
9
Dimensions - mm
Operating voltage
Disengages
Engages
Fault-sensing
Operating Temp.
Digital Voltage Sensitive Relay
Possible Cause
Poor/Reversed connection to
vehicle battery
OR
Incoming power Voltage not high
enough to engage DVSR
Incoming power voltage is above
upper limit of operating voltage.
12vDC Main Supply
9-15vDC
12.8vDC
13.4vDC
Model 08879
Check connection and of battery
lead and any extension cables.
Test voltage of primary power
supply.
Charge or replace primary batteries.
Check main supply voltage.
24vDC Main Supply
68L x 68W x 50D
Indicators for Power Source(s) Only
-40 to 85ºC
Rev 1.0
Solution
16-32vDC
25.6vDC
26.8vDC