4. Non-synchronizable NAC Appliances:
When using NAC appliances not designed to support synchronization feature, it is recommended to use separate out-
put circuits for audible notification appliances (horns) and visual notification appliances (strobes). Set dip switches for
the visual notification appliances to follow Input 1 [IN1] and for audible notification appliances to follow Input 2 [IN2].
This will allow, when using two (2) outputs from the FACP, to support silencing of audible notification appliances.
When using only one (1) FACP output, set all dip switches to follow Input 1 [IN1]. The units outputs can each be set for
the desired NAC drive signal, such as Code 3 or march time sequence (Output Programming Selection Table, pg. 6).
Non-synchronizable Audible Appliances will follow the sequence, when feature is selected.
5. Synchronizing One (1) or More NAC Power Extenders from an FACP with Sync Capability
or a Sync Module:
AL602/802/1002ULADA units are designed to follow (replicate) the coded sequence, generated by a manufacturer's
sync module. One (1) or more units can be synchronized. Please select Input to Output follower mode (Output
Programming Selection Table, pg. 6). Connect the output of the sync module to Input 1 or Input 2, depending which
input is selected to drive the outputs. Terminate the input circuit with the EOL, connecting it to terminals marked [RET+
and RET-], or continue the input circuit, connecting to terminals marked [RET+ and RET- to INP+ and INP-] of the next
unit, when multiple units need to be synchronized.
Fig. 5
FACP with Sync Output
FACP
(Fire Alarm
Control Panel
with sync
capabilities)
Or
Sync Module
POWER
POWER
IN +
POWER
POWER
IN ---
POWER
POWER
IN +
POWER
POWER
IN ---
NAC Power Extender:
Dip Switches set for Input to Output Follower Mode.
OUT +
OUT ---
OUT +
OUT ---
2.2K
2.2K
EOL
EOL
2.2K
2.2K
EOL
EOL
- 3 -
NAC Power Extender:
Dip Switches set for Input to Output Follower Mode.
2.2K
2.2K
2.2K
2.2K
EOL
EOL
EOL
EOL
To FACP EOL or
next NAC power extender