Quick Setup Guide
Installation Location
CAUTION: This alarm will only indicate the presence of electricity in the range of the sensor. Stray
Electricity may be present in other areas.
IMPORTANT: Improper location can affect the sensitive electronic components in this alarm.
Sensing Probe Location
The Sensing Probe lead wire can be lengthened to allow for placement of the probe in the optimal
location on your dock. It is suggest positioning the probe closer to the location under the dock where
people are swimming or using the ladder. Place the probe deep enough in the water so that it will still
be submerged when your lake is in a low water situation.
Avoid running sensing wire parallel to other wires to avoid cross coupling.
Metal Floating Docks
Pier Docks with Wood Pilings
Installation of Dock Lifeguard unit should be done by mounting the unit near an outlet under roof if
possible by using screws installed through the upper and lower mounted points on the unit. Dock
Lifeguard needs to be bonded to the safety ground system of the dock; this is accomplished through the
lower installation point on the unit (green ground reference wire). It is recommended to connect the
ground lead (green wire) of the Dock Lifeguard unit to the electric equipment ground of the receptacle
being used to power the Dock Lifeguard unit. Note: You must have a proper bond from the Dock
Lifeguard to the dock safety ground.
Pier Docks with Metal Pilings
Installation of Dock Lifeguard unit should be done by mounting the unit near an outlet under roof if
possible by using screws installed through the upper and lower mounted points on the unit. Dock
Lifeguard needs to be bonded to the safety ground system of the dock; this is accomplished through the
lower installation point on the unit (green ground reference wire). It is recommended to connect the
ground lead (green wire) of the Dock Lifeguard unit to the electric equipment ground of the receptacle
being used to power the Dock Lifeguard unit. Note: Docks constructed with metal pilings may require
Installation of Dock Lifeguard unit should be done by mounting the unit
on a roof support system (Metal Post) under roof if possible near an
outlet by using metal screws installed through the upper and lower
mounted points on the unit. Dock Lifeguard needs to be bonded to the
safety ground system of the dock; this is accomplished through the green
ground reference wire on lower installation point on the unit. It is
recommended to bond the ground lead (green wire) of the Dock Lifeguard
unit to the frame of the grounded dock and to the ground of the electrical
system of the dock. Note: You must have a proper bond of the dock
lifeguard green wire to the dock safety ground for correct operation.