Ashcroft CXLdp Fiche d'installation et d'entretien - Page 2

Parcourez en ligne ou téléchargez le pdf Fiche d'installation et d'entretien pour {nom_de_la_catégorie} Ashcroft CXLdp. Ashcroft CXLdp 2 pages. Differential pressure transducer
Également pour Ashcroft CXLdp : Fiche d'installation (2 pages)

MODEL CXLdp DIFFERENTIAL
PRESSURE TRANSDUCER
INSTALLATION & MAINTENANCE SHEET
Set Up:
Note: For best immunity from EMI the pressure
connection fittings on the CXLdp should not be
grounded.
The transducers are calibrated at the factory in the
vertical position. Mounting in the horizontal position
can cause a zero shift of as much as ±1% F.S. in
ranges below 1 IW dp. Any minor zero offset can
be minimized using the zero adjust potentiometer
located on the front, left side of the instrument.
To find true zero differential pressure, pneumatically
connect the high and low pressure connections
together using the tubing provided with the trans-
ducer. The barbed connection accept
tubing.
(see Figure 5)
Figure 5
When
NPT female
1
8
brass fittings are
used, do not ex-
ceed 60 inch-pound
torque force on fe-
male NPT fitting.
When connecting
to the NPT fittings,
do not apply torque
to the CXLdp fitting.
Use a
˝ wrench to
9
Figure 6
1 6
hold the CXLdp. (see
Figure 6)
Zero potentiometer
adjustment requires
using a
˝ or 2.5mm
3
3 2
slotted or phillips
screwdriver. The
tubing should
remain in place until the transducer is to be con-
nected to the BCS tubing system.
(see Figure 7)
© 2022 Ashcroft Inc. 250 East Main Street 06614, Tel: 203-378-8281 • Fax: 203-378-0499, all specifications are subject to change without notice.
All sales subject to standard terms and conditions. www.ashcroft.com All rights reserved. (cxldp_transducer_i&m_(011-10130)_RevF_12-16-22
Zero and Span Potentiometers
Figure 7
ZERO
Zero adjust
potentiometer
Routine Maintenance:
The CXLdp is a very stable and reliable transducer
incorporating a proven, micro-machined silicon
capacitive sensor and a new, state-of-the-art appli-
˝ O.D.
˝ I.D.
1
1
4
8
cation specific integrated circuit (ASIC).
All calibration and temperature compensation func-
tions are done with a microprocessor and
digital routines.
To troubleshoot or verify performance, it is rec-
ommended to pneumatically connect the pressure
ports to each other and establish a zero offset read-
ing in the as-installed position. Adjusting zero will
not affect span calibration.
Adjusting span should only be attempted when a
high accuracy pressure standard and high quality
electrical meter are able to be used.
DIN Rail Transducer Removal:
In order to remove the transducer when it is installed
on a DIN rail, it is necessary to first unplug the wiring
terminal block from the transducer .
Insert a small slot-
ted screwdriver into
the black plastic clip
extending slightly
below the trans-
mitter case. (see
Figure 8)
Next, raise the
screwdriver handle
up thereby forcing
the spring clip
down.
If questions or concerns need to be addressed, our
Low Pressure Product Manager or Engineering Per-
sonnel can be contacted at (203) 378-8281 or visit
our website at www.ashcroft.com.
SPAN
Span adjust
potentiometer
0.16˝
0.56˝
Figure 8
GENERAL DIMENSIONS FOR
MODEL CXLdp (in inches)
MB2
˝ BARB FITTINGS
1
"B2" ¼ BARB FITTINGS
4
1.45˝
0.20˝
POWER
HI
LO
3.30˝
2.90˝
ZERO
SPAN
1.89˝
F01
NPT FEMALE FITTINGS
1
8
"01"
1
FEMALE NPT FITTINGS
8
1.45˝
POWER
LO
HI
3.30˝
ZERO
SPAN
2.90˝
1.89˝
ASSEMBLED WITH 101A213-01
CONDUIT KIT
ASSEMBLED WITH 101A213-01 CONDUIT KIT
4.85
4.85
0.16˝
2.06
2.06
R R .88 .88
.78 .78
0.37˝
1.32˝
HOUSING TABS (2)
0.37˝
1.32˝
HOUSI