2.3
Setting the Deadband Control Pressure
The WPT-DB thermostat extends the functions of the conventional WPT thermostat by
allowing a temperature range to be programmed where no heating or cooling takes
place. This range is known as the Deadband. All pneumatic systems will have a neutral
control pressure (control point), typically ~8psi, where the zone is neither heated nor
cooled. If the branch pressure is held at this control pressure, the zone will use a
minimal amount of energy. The Deadband Control Pressure is set during calibration.
See sec 2.4 for calibration details.
20psi
Control Pressure
0psi
Heat Below
2.4
Calibrating the WPT-DB
1. Remove the front cover of the WPT-DB and make sure that the WPT-DB is
acclimatized to the ambient temperature.
NOTE: This can take 5 to 10 minutes after attachment to the wall. The bi-metallic spring
is very sensitive to body heat. Keep hands and breathe away from WPT-DB to
minimize calibration error.
NOTE: The black throttling range adjuster has been factory set to the location marked
on the lever as shown in Figure 14. The factory setting provides a Throttling
Range (TR) of 4° F. This TR adjuster MUST NOT BE MO VED in order to ensure
proper operation and accuracy of the WPT-DB.
2. To enter Calibration Mode, perform the following:
Press the ▼ button and OVR button together for two seconds. The display will
show 'dt'.
Heat Below
Setpoint
Figure 12: WPT-DB transfer function
WPT-DB Installation Manual
Document No. 910-00014-01, Rev. 04
Deadband
Span
Temperature
Deadband
Cool Above
Setpoint
Cool Above