NOTE: The network ID cannot have a "0" value.
3. Press OVR to confirm the network ID. This completes the programming of the
network ID and the LCD displays the first digit, D1, of the node ID.
NOTE: ° C icon is displayed, indicating that the node ID is being programmed.
4. Press the ▲ or ▼ button to change D1 to the required value.
NOTE: D1 cannot have an "F" value.
5. Press OVR to confirm D1.
6. Repeat steps 4 and 5 to configure D2, D3, and D4 of the node ID.
NOTE: While the node ID is being configured, the corresponding bar of the battery
indicator flashes.
7. After D4 is configured and confirmed, continue to press OVR to exit the
Programming Mode.
NOTE: The WPT-DB will automatically exit the Programming Mode if no button is
pressed for one minute.
The network and node IDs can be changed any time by completing steps 1 through 7.
2.2.3
Selecting between Celsius and Fahrenheit display
The WPT-DB can display temperatures in Celsius or Fahrenheit. The default setting is
for Fahrenheit. To toggle the setting:
Figure 11. Configuring Node ID 4321