CO2 Meter RAD-0501A Petunjuk Pengoperasian - Halaman 3

Jelajahi secara online atau unduh pdf Petunjuk Pengoperasian untuk Pengontrol CO2 Meter RAD-0501A. CO2 Meter RAD-0501A 4 halaman. Co2 controller

CO2 Meter RAD-0501A Petunjuk Pengoperasian
14. Specifications
CO2 Specification
0 - 2,000ppm for rated specifications
Measurement Range
0 - 10,000ppm output for 4-20mA output
Display Resolution
1ppm at 0~1,000ppm; 10ppm above 1,000ppm
0 - 2,000ppm: ±70ppm or ±5% of reading,
Accuracy
whichever is greater. >2,000ppm: ±7% of reading
Repeatability
±20ppm @400ppm
Pressure
0.13% of reading per mmHg
Dependence
Response Time
< 2 minutes for 63% response to step change
RAD-0501 Greenhouse Mode = 1,000ppm
SetPoint
RAD-0501A Ventilation Mode = 1,200ppm
SetPoint Hysteresis
± 200ppm around Target
Sensor Warm-Up Time
< 60 seconds at 72°F (22°C)
Splash Rating
IP54 non-sealed enclosure
Operating Conditions:
Temperature
32°F to 122°F (0°C to 50°C)
Humidity
0 ~ 95% RH non-condensing
Storage Conditions:
Temperature
-4°F to 140°F (-20°C to 60 °C)
Power Supply & Relay Output:
Power Supply
AC adapter 110/220 VAC (U.S. Only)
Voltage
100 ~ 240 VAC
AC
Frequency
50 / 60 Hz
Input
Power
1 W maximum @ 115 VAC 60 Hz
Requirement
2 W maximum @ 230 VAC 50 Hz
Peak Current < 5A@ 250 VAC, SPST.
Relay (Piggyback plug)
Normally Open.
Linear current 4-20mA = 0-10,000ppm.
Analog Output
RL < 150Ω. Red (+) signal, White ground.
15. Dimensions
16. Error Codes & Troubleshooting
LCD
Description
No
Fault
(of the fault)
Icon
The ambient temperature
has exceeded the
1
Er3
temperature range 0°C to
50°C ( 32°F to 122°F)
Inaccurate measurement
2
Er4
or the sensor has
exceeded its expected life
Er5
3
EEPROM System Problem
Er6
The accuracy of CO2
4
Er8
sensor may deviate from
the actual concentration.
Calibration failure caused
by too large a difference
between the calibration
5
Er9
value selected and the
CO2 level read during
calibration.
3
Suggested Actions
This error will disappear when the
temperature returns to the range
between 0°C and 50°C (32°F to
122°F).
Unplug the AC adapter and
reconnect it. If Er4 still appears,
contact CO2Meter.com.
Unplug the AC adapter and
reconnect it. If Er5 or Er6 still
appears, contact CO2Meter.com.
1. Unplug the AC adapter and
reconnect. If the "Er8" still
appears, recalibrate.
2. Calibrate the unit. If the "Er8" still
appears, contact CO2Meter.com.
1. Select the correct calibration
value before calibrating.
2. If Er9 still appears, contact
CO2Meter.com