5. Add next sections of pipe until end penetrates roof line. Check to see
that proper clearances are maintained. Extend chimney by adding
sections of double wall pipe until pipe is minimum of 30" above
highest point of roof cutout. Termination and chimney must extend
a minimum of 36" above highest point where it passes through the
roof (see 10-Foot Rule and Figure 20, page 10.
19" Min.
(48.26cm)
2" Min.
(5.08cm)
2" Min.
(5.08cm)
Pitch
Slope Opening "A"
Flat
0-6/12
26.6°
6/12-
45°
12/12
Figure 22 - Roof Opening Measurements
FLASHING INSTALLATION
Determine flashing to be used with roof opening chart. Slide flashing
over pipe until base is flat against roof. Replace as many shingles as
needed to cover exposed area and flashing base. Secure in position
by nailing through shingles (see Figure 23). DO NOT NAIL THROUGH
FLASHING CONE.
Storm Collar
Flashing
Cone
Nail Only Outer
Perimeter of
Flashing
Underlap Shingles
at Bottom
Figure 23 - Flashing Installation
126650-01A
VENTING INSTALLATION Continued
30" Min.
(76.2cm)
2" Min.
(5.08cm)
Opening
"A"
Used Flashing
Max.
Model No.
19"
V6F-8DM
23.25"
V6F-8DM
30.75"
V12F-8DM
Overlap
Shingles Top
and Sides Only
STORM COLLAR INSTALLATION
Place storm collar over pipe and slide down until it is snug against
the open edge of the flashing (see Figure 24). Apply waterproof
caulking to all seams and notches around storm and also at base
around shingles.
Chimney
Pipe
Storm
Collar
TERMINATIONS
Standard Installation
The fireplace system must be terminated with the listed round top or
chase terminations. In any case, refer to the installation instructions
supplied with the termination.
Terminations approved for this fireplace are RTL-8DM and RTTL-
8DM, which can be used for flashing or chase and ETO-8DM and
ETLO-8DM for chase style termination only. Figure 25, shows a
RTL-8DM round top termination.
Follow installation instructions provided with termination being used.
CAUTION: Do not seal openings on the rooftop
flashing. Follow the installation instructions provided
with the termination being used.
Stainless
Inner Flue
Pipe
Secure
Termination
to Outer
Pipe with 3
Screws
Overlap
Shingles (Top and
Sides of Flashing Base)
www.Astria.US.com
Waterproof
Caulk
Figure 24 - Storm Collar
Chase
Top
1" Non-
com-
bustible
Spacer
Figure 25 - Terminations
Flashing
RTL-8DM
Screen
1"
Space
Apply
Waterproof
Caulking
Storm
Collar
Flashing
Underlap
Shingles
11