CHASE INSTALLATIONS
Instructions for chase installations are included with the chase style
termination chosen. In a multiple chase installation, be sure to provide
adequate distance between terminations to prevent smoke spillage
from one termination to another. Terminations must be separated a
minimum of 30" center to center and stacked at a minimum vertical
height difference of 18" (see Figure 26).
Note: If a decorative shroud is to be installed, contact the manufac-
turer for specifications.
30" Min.
30" Min.
Figure 26 - Multiple Chase Installation
FINISHING FIREPLACE
Installing Fireplace Facing.
Any noncombustible material may be used for facing (glass, tile,
brick, etc.) as long as proper clearances are adhered to and firebox
openings are not obstructed in any way (see Figure 27).
Use only heat resistant, noncombustible mortar or adhesive when
securing facing material to front of firebox. When placing facing at
upper edge of effective opening of firebox, provide "L" shaped piece
of metal extending full width of opening (see Figure 27).
Secure with sheet metal screws at a distance high enough from
edge so it doesn't interfere with operation of doors. This assures
that facing material will not block openings.
12
VENTING INSTALLATION Continued
18"
Figure 27 - Fireplace Facing (Your Fireplace May Vary from
Min.
Typ.
www.Astria.US.com
Noncombustible
Facing Material
"L" Shaped
Do Not
Metal
Block
Support
Opening
Noncombustible
Facing Material
Illustration)