Dorex DX KA Petunjuk Instalasi - Halaman 2
Jelajahi secara online atau unduh pdf Petunjuk Instalasi untuk Sistem pembukaan pintu Dorex DX KA. Dorex DX KA 4 halaman.
01. COMPLETE WIRING (IF REQUIRED)
Drill 5/8"dia. wire access hole thru device side of door.
Power
Transfer
Route cable through hole and connect wires to power transfer
(see "POWER TRANSFER" instructions as needed).
NOTE: Alarm Exit Device does not contain dogging option.
03. ATTACH WIRING TO TERMINAL BLOCKS ON ALARM EXIT MODULE
RX Switch
(Normally open contact)
COM
Red
NO
NC
Yellow
Blue
OR
Contacts RX/LM
terminal block
LM Switch
(Normally open contact)
COM
White
NO
NC
Violet
Gray
5/16"
5/8" Diameter
L C
External Inhibit
(Normally open contact)
COM
NO
EI
RX/LM
12VAC/24VAC
12VDC/24VDC
Power Supply
(PS101/PS102 Class 2 Power Supply)
NOTE: 1. The external inhibit (EI) option uses normally open (NO) dry access control
contacts to inhibit the AL.
2. Closing the access control contacts inhibits the AL. When the access control
contacts are re-opened, the AL re-arms with no delay.
3. All terminal inputs are not polarized.
02. INSTALL CYLINDER AND BATTERY
9 Volt
Battery
Cylinder
Lock Nut
Thread cylinder lock nut onto mortise cylinder. Make
sure to fasten down tight.
Check if polarity
is correct
IMPORTANT: Before installing battery, make sure
transmitting cam is in OFF position.
NC
2
1-1/4" Mortise
Cylinder
Transmitting
Cam
+
+
-
-
Switch OFF
Position