Advanced Air 0160 Series Panduan Pemasangan, Pengoperasian, dan Pemeliharaan - Halaman 4

Jelajahi secara online atau unduh pdf Panduan Pemasangan, Pengoperasian, dan Pemeliharaan untuk Peredam Api dan Asap Advanced Air 0160 Series. Advanced Air 0160 Series 13 halaman. Air control fire damper
Juga untuk Advanced Air 0160 Series: Panduan Memulai Cepat (14 halaman)

Advanced Air 0160 Series Panduan Pemasangan, Pengoperasian, dan Pemeliharaan
FIRE – 0160 ADJUSTABLE FRAME SYSTEM FOR TWO HOUR FLEXIBLE SUPPORTING CONSTRUCTION (SUPPORT ONE SIDE)
M10 drop rod
Access door for
inspection / damper reset
0160 W/ AFS RAIL
PRODUCT
TBA
CLASSIFICATION REPORT NO.
TESTED INSTALLATION METHOD SHOWN. DIFFERING INSTALLATION METHODS TO THIS MUST BE APPROVED BY THE BUILDING CONTROL AUTHORITY (BCA) BEFORE PROCEEDING.
Preparation
1
2
3
Two layers of 50mm thick
140kg/m fire batt
Installation sequence
4
Patented Adjustable Frame System (AFS)
5
incorporating bracket, bracket slot, and
Z-piece (Patent No: GB2557865)
AFS rail
6
7
0160 Series fire damper
8
9
10
11
12
Two hour rated flexible
supporting construction
to BS EN 1363-1:2020
13
Steel stud depth – 71 to 100mm
14
15mm thick gypsum boards
15
FLEXIBLE SUPPORTING CONSTRUCTION
APPLICATION
E120 (VE I  O)
CLASSIFICATION
Nom. duct width
100-1,000mm
Ensure that the damper is kept
in a clean dry environment and
Nom. duct height
that there is no damage to the
100mm
damper.
101-300mm
Remove all the packaging and
301-525mm
transit ties before installation.
526-700mm
701-925mm
Work out the opening size to be
926-1,000mm
cut using the adjacent table.
The drywall will consist of two layers of 15mm plasterboard each side of steel studwork with an
optional mineral wool insulation. The opening will be a letterbox construction with overlapping layers
of plasterboard with an opening clearance around the damper casing in line with the above table.
Two M10 drop rods per fire damper shall be fitted on one side of the drywall. These should be securely
installed in line with the manufacturer's fixing instructions in a position to match the AFS rail.
The drop rods should have a nut screwed on for clamping the rail from above.
Slide the AFS rails on each side of the damper into the brackets and insert the "Z" piece into the
bracket slot pushing it up against the underside of the rail. Insert the 8mm bolt from above into the slot
through the "Z" piece fitting the nut until tight to secure the rail.
The damper should be mounted centrally in the opening flush with the wall on the side with the drop
rods, as detailed in the drawing. The drop rods are to slide through the slots in the rail and a nut
screwed on to take the support of the damper rail. The damper must then be levelled and when in the
correct position the nut above the rail should be tightened against the rail.
The galvanised mild steel ductwork connecting to the damper spigots must overlap by up to 40mm,
leaving a minimum 10mm clearance for any duct expansion in a fire situation.
The galvanised mild steel ductwork connections must be sealed with an approved galvanised mild
steel ductwork sealer and fixed with low resistance fixings such as aluminium rivets that will melt at
high temperature allowing the duct to break away without effecting the integrity of the installation.
The connecting galvanised mild steel ductwork must be independently supported within one metre of
the connections and have been installed in accordance with DW144.
The gap between the damper and the wall opening will need filling with two layers of 50mm thick
140kg/m3 fire batt cut to an interference fit and pushed in to place. All cut edges must be sealed with
a firebatt sealant to BS EN 13501-2. A fire rated intumescent mastic to BS EN 13501-2 shall be applied
to each joint.
An access door should be fitted on the access side of the damper to enable the resetting of the
damper blades.
When the damper installation has been completed checks should be made to ensure the AFS rails are
secure and there is no movement, operation of the damper should be checked.
Complete DW145 Fire Damper Certificate.
Opening width min.
Opening width max.
Nom. duct +194mm
Nom. duct +350mm
Opening height min.
Opening height max.
Nom. duct +100mm
Nom. duct +350mm
Nom. duct +125mm
Nom. duct +375mm
Nom. duct +150mm
Nom. duct +400mm
Nom. duct +175mm
Nom. duct +425mm
Nom. duct +200mm
Nom. duct +450mm
Nom. duct +225mm
Nom. duct +475mm
4