Juga untuk Bosch FAP-OC 500Series: Panduan Petunjuk Instalasi (21 halaman), Petunjuk Penggunaan Manual (40 halaman), Panduan Instalasi (6 halaman), Panduan Instalasi (28 halaman), Panduan Pengguna (48 halaman), Panduan Pengguna (48 halaman), Panduan Instalasi (28 halaman), Panduan Penggunaan dan Perawatan (44 halaman), Panduan Instalasi (32 halaman), Panduan Penggunaan dan Perawatan / Petunjuk Pemasangan (40 halaman), Panduan Referensi Cepat (4 halaman), Panduan Penggunaan dan Perawatan (27 halaman), Panduan Instalasi (24 halaman), Panduan Instalasi (32 halaman), Panduan Penggunaan dan Perawatan (24 halaman), Panduan Instalasi (28 halaman), Panduan Servis (41 halaman), Panduan Penggunaan dan Perawatan (21 halaman), Panduan Instalasi (32 halaman), Panduan Servis (36 halaman), Panduan Instalasi (32 halaman), Panduan Memulai Cepat dan Keselamatan (13 halaman)

Bosch FAP-OC 500Series Informasi Produk
Product Information 500 Series LSN Fire Detectors (EU)

7.2. General Notes for Detector Testing

FAP−OC 500
The
The CO sensor provides improved response behavior and increased stability against
nuisance alarms in critical environmental conditions.
For fire detection, FAP−500 detectors use the time behavior of the fire characteristics,
which differs from the time behavior of disruption variables.
Therefore, for a functional test, the detector must be switched to test mode. Switching
to test mode can occur in two ways, which are described in the alternative test proce-
dures (see below).
Detectors that are programmed for two−detector dependency must be
tested in accordance with the first alternative (in test mode).
For the detector test, you need:
− detector test device for optical fire detector (product ID 4.998.112.071)
− FAA−500−TTL test adapter with magnet (product ID F.01U.508.725).
For OC detector, in addition:
− CO testing gas for detector with CO sensor (product ID 4.998.142.221).
detector has an additional sensor for CO detection in case of fire.
Page 34
PI − 34.70 en
BDL−F.01U.025.876
A5.en/ 02.02.2006
ST−FIR/PRM1 / zab