Juga untuk Bosch FAP-OC 500Series: Panduan Petunjuk Instalasi (21 halaman), Petunjuk Penggunaan Manual (40 halaman), Panduan Instalasi (6 halaman), Panduan Instalasi (28 halaman), Panduan Pengguna (48 halaman), Panduan Pengguna (48 halaman), Panduan Instalasi (28 halaman), Panduan Penggunaan dan Perawatan (44 halaman), Panduan Instalasi (32 halaman), Panduan Penggunaan dan Perawatan / Petunjuk Pemasangan (40 halaman), Panduan Referensi Cepat (4 halaman), Panduan Penggunaan dan Perawatan (27 halaman), Panduan Instalasi (24 halaman), Panduan Instalasi (32 halaman), Panduan Penggunaan dan Perawatan (24 halaman), Panduan Instalasi (28 halaman), Panduan Servis (41 halaman), Panduan Penggunaan dan Perawatan (21 halaman), Panduan Instalasi (32 halaman), Panduan Servis (36 halaman), Panduan Instalasi (32 halaman), Panduan Memulai Cepat dan Keselamatan (13 halaman)

Bosch FAP-OC 500Series Informasi Produk
Product Information 500 Series LSN Fire Detectors (EU)
2. Alternative
D The detector can be tested in normal operation if a test device with magnet is used.
Make sure that the alarm cannot be passed on to higher−level systems.
Programmed activations of the central unit are retained and will be executed.
D Figure 22. shows the position of the reed switch (Pos. R) in the case of OC
detectors.
. If you imagine the CO sensor (Pos. CO) to be in a 12 o'clock position, the reed
switch (Pos. R) is located at approximately 2 o'clock.
22.
D Bring the magnet close to the reed switch.
D The LED of the detector flashes green once a second as soon as the reed switch
has been triggered.
. The detector will now remain in test mode for 60 sec with automatically set test pa-
rameters (e.g. reduction of the delay time to 15 sec). The green LED flashes for as
long as the detector remains in test mode.
D Now hold the test device under the detector so that the test beaker is flush with the
trim ring and seals it tightly.
. Make sure that the test beaker does not tilt, which could cause the detector
to be lifted up and consequently become detached from its fastening.
D Proceed as in the case of the first alternative:
− spray with CO gas
− leave the test device on the detector for approx. 20 sec, until the alarm is triggered.
. In the case of programmed intermediate alarm storage, longer trigger times occur.
D Both scattered light areas are covered by the test beaker, so that both optical sensors
are triggered as the same time as the CO sensor (no O testing gas is required).
D The detector triggers the alarm and the red alarm LED flashes.
CO
LED