Anderson VFC86 Panduan Pengoperasian - Halaman 10

Jelajahi secara online atau unduh pdf Panduan Pengoperasian untuk Pembakar Anderson VFC86. Anderson VFC86 12 halaman.

– Test the manual gas shut off cocks for proper operation.

10.2 Yearly checklist

– Leak test the safety shut-off valves and pipe for tightness of closure to make sure no
leakage.
– Test the pressure switch settings by checking the switch movements against
pressure settings and comparing these with the actual impulse pressure.
– Visually check igniter cable and connectors.
– Be sure the burner bodies and air wings, the ignite and the flame sensors are not
damaged or distorted.
Anderson Thermal Soluions(Suzhou)Co., Ltd
Anderson Thermal Solutions – VFC86 Burner Operation Manual
8