SYMPTOM
Cabinet too warm
Cabinet too cold
Water in the bottom of
the unit
Service Manual for Refrigerated Back Counter RBC 48/60
TROUBLESHOOTING
CAUSE
Unit not plugged in
Thermostat set too warm
Faulty thermostat, in the
coldest position, the switch is
not closed
Doors not sealing
Torn or damaged door
gaskets
Evaporator fan not running
Condenser fan motor not
running
Condenser coil dirty/ filter dirty
Refrigerant leak
Thermostat set too cold
Faulty thermostat, in the off
position, the switch does not
open, stuck closed
Drain tube plugged
Drain tube loose or
disconnected from drain pan
REMEDY
Plug unit in
Set thermostat colder, the
higher the number, the
colder the unit will be
Replace thermostat
Adjust doors
Replace gaskets
Check motor, repair or
replace
Check motor, repair or
replace
Clean coil or filter
Leak check unit, repair,
and recharge
Turn thermostat to a
warmer setting, the higher
the number, the colder the
unit will be
Replace thermostat
Clear drain tube
Tighten or re-connect
drain tube
11