Juga untuk Danfoss iC7 Series: Panduan Instalasi (8 halaman), Panduan Instalasi (8 halaman), Panduan Instalasi (6 halaman), Panduan Instalasi (14 halaman), Panduan Instalasi (16 halaman), Panduan Instalasi (8 halaman), Panduan Instalasi (10 halaman), Panduan Instalasi (16 halaman), Panduan Instalasi (16 halaman), Panduan Instalasi (6 halaman), Panduan Instalasi (6 halaman), Panduan Instalasi (16 halaman), Panduan Instalasi (18 halaman)

Danfoss iC7 Series Panduan Instalasi
Tall Pedestal Kit for FK11/FB11 and FK12/FB12
Installation Guide
1
Cabinet
2
Pedestal
8.
To secure the top of the frequency conveter, fasten 3 M10 bolts at the upper back edge of the cabinet.
2.6 Creating Cable Openings
The cable entry plate provides cable entry and cable termination points, and must be installed to maintain the IP21/Type 1 or IP54/
Type 12 protection rating. The cable entry plate is placed between the frequency converter cabinet and the pedestal.
Depending on stud orientation, the plate can be installed from inside the cabinet or by taking off the front cover of the pedestal. To
prepare and install the cable entry plate, use the following steps. Refer to
1.
Create cable entry holes in the plate using a sheet metal punch.
2.
If installing the cable entry plate through the pedestal, remove 6 M5x14 countersunk screws that secure the pedestal front
plate.
3.
Insert the cable entry plate using 1 of the following methods:
a.
Slide the cable entry plate through the slot in the front of the pedestal.
b.
Insert the cable entry plate through the cabinet, angling the plate until it slides under the slotted brackets.
4.
Align the studs on the cable entry plate to the holes in the pedestal and secure with 10 M5 nuts.
Torque each nut to 2.3 Nm (20 in-lb)
5.
Fasten the front plate to the pedestal with 6 M5x14 countersunk screws.
1
2
3
Illustration 5: Cable Entry Plate Installation
1
Cable entry plate
2
Cable entry hole
3
M5 nut
6 | Danfoss A/S © 2022.03
3
M10x22 screws (rear corner bolts not shown)
Illustration
5.
4
5
6
4
Slot in pedestal
5
Front cover
6
M5 countersunk screw
AN361529835714en-000101 / 136R0257