AddSecure Edge RT7020 Enterprise Panduan Pengguna - Halaman 9
Jelajahi secara online atau unduh pdf Panduan Pengguna untuk Sistem Keamanan AddSecure Edge RT7020 Enterprise. AddSecure Edge RT7020 Enterprise 11 halaman.
8 Technical Specifications Edge RT7020 Enterprise
8.1
Connections
Connection
LINE
D+ D-
T C
REL5
REL4
REL3
REL2
REL1
IN1-IN8
C
O1-O4
BAT+ -
PWR+ -
J7
J8
J6
Function
Simulated telephone line for connecting of analogue dialer. Designed for a local
direct connection, i.e. not for connections between buildings.
RS-485 interface for communication to/from external equipment.
T: For connecting external tamper (if such is present) C: Common (GND)
Normally open. Indicates a successful transmission of IN1 to ARC by closing for 2s
Normally open. Indicates an unsuccessful transmission of IN1 to ARC by closing
for 2s
Normally closed. Is held open if alarm transmission has failed or if it is not
possible to perform via the radio interface.
Normally closed. Is held open if alarm transmission has failed or if it is not
possible to perform via Ethernet.
Normally closed. Is held open during system fault. Meaning when an alarm can't
be delivered to the ARC neither by the radio or the Ethernet interface
Alarm inputs 1-8. Activated by potential free closing or opening from system
ground (C) and/or tamper, depending on how the inputs have been configured
during programming.
System ground (GND)
Remotely controllable potential free outputs. Max current: 100mA per output
Connection for auxiliary power source, max 11-30 VDC. To be fused with an
external fuse 1A and labelled with what part of the unit that becomes unpowered
when removing the fuse.
Connection for primary power source, max 11-30 VDC. To be fused with an
external fuse 1A and labelled with what part of the unit that becomes unpowered
when removing the fuse
WAN-connector, connection to local network
LAN-connectors, for connecting local IP equipment
RS-232 interface for communication from external system.
9