Jelajahi secara online atau unduh pdf Panduan Memulai Cepat untuk Beralih Bender ATICS-2-ISO Series. Bender ATICS-2-ISO Series 8 halaman. Automatic transfer switching devices with monitoring functions for unearthed safety power supplies - software version: d333 v1.3x, d334, v1.3x, d335 v1.0x, d308 v1.2x
Juga untuk Bender ATICS-2-ISO Series: Panduan Memulai Cepat (16 halaman)

ATICS-2...-ISO Quick start
11. Connection example basic configuration
Terminal
Meaning
1, 3
Connection for Line 1 (input line) L, N
5, 7
Connection for Line 2 (input line) L, N
4, 6
Connection for Line 3 (output line) N, L
l, k
Connection measuring current transformer T3 (STW3) for monitoring the load current downstream the transfer switching device
(short-circuit monitoring)
GND, En/Ex
Connection must not be used. These terminals are solely intended for future extensions!
IN1/GND, IN1 Digital input, configurable, for example, for monitoring the switch position of the transfer switching device
NC
not used
L1/IT, L2/IT
Connection to the IT system. Monitoring the insulation resistance. When there are insulation faults: Locating current fed in for
insulation fault location. Bipolar protection via 6 A back-up fuse.
E, KE
Connection of E and KE to two separate PE lines.
The terminals labelled GND must not be connected to PE.
Z1, Z2
Temperature monitoring for the IT system transformer
k/IT, l/IT
Connection for measuring current transformer STW2 to monitor the load current downstream of the IT system transformer (overload monitoring)
A, B
BMS bus connection
NC
not used
14, 12, 11
Alarm relay, programmable function
Alle Rechte vorbehalten. Nachdruck und Vervielfältigung nur mit
Genehmigung des Herausgebers. Änderungen vorbehalten!
©
Bender GmbH & Co. KG
Fotos: Bender Archiv.
Bender GmbH & Co. KG
P.O. Box 1161 • 35301 Gruenberg • Germany
Londorfer Strasse 65 • 35305 Gruenberg • Germany
Tel.: +49 6401 807-0 • Fax: +49 6401 807-259
E-mail: [email protected] • www.bender.de
4
All rights reserved. Reprinting and duplicating only with
permission of the publisher. Subject to change!
ATICS-2-ISO_D00046_02_Q_XXEN/09.2016
©
Bender GmbH & Co. KG
Photos: Bender archives.