The High Temperature Input can be wired to either a NO (normally open) or NC (normally closed) switch
(must be correctly defined in software), the switch must be the type that closes to ground on failure. A failure
delay can be set in software to be certain that a failure has actually occurred; the delay can be set from 0.5 to 6
seconds in 0.5 second increments.
NOTE: The High Temperature Input failure is disabled during the failure bypass time.
AUXILIARY INPUTS
There are two available Auxiliary Inputs which can be configured to either indicate a warning or generate a
failure in software. Both of these inputs can be wired to either a NO (normally open) or NC (normally closed)
switch (must be correctly defined in software), the switch must be the type that closes to ground on failure. A
failure delay can be set in software to be certain that a failure has actually occurred; the delay can be set from
0.5 to 6 seconds in 0.5 second increments.
NOTE: The Auxiliary Input failures are disabled during the failure bypass time.
HOUR METER
The hour meter displays the total accumulated generator run time. The display represents both hours and
minutes in the form 1234.5. The last digit on the hour meter will represent the time in 1/10's of an hour. Please
note that the accumulated time displayed on the hour meter can not be reset.
EXERCISER FUNCTION
The exerciser function is programmable only through the front panel buttons. When the controller is first
powered up in Auto mode the Engine Run LED will flash to indicate that the Exerciser Function has not been
programmed if not already programmed. There are four intervals for the Exerciser selectable, once a week, once
every 2 weeks, once every 3 weeks and once every 4 weeks. At programming you must make note of the time
of the Exercise event as there is no way to retrieve that information once programming is complete. The
exercise cycle will last for 15 minutes plus the Cooldown period (if Cooldown enabled). The exercise cycle can
be interrupted by pressing the OFF button during the cycle, but the controller will resume the cycle if returned
to AUTO with time remaining in the cycle. How to program the Exerciser Function is explained later in the
manual.
TRANSFER SWITCH CONTROLS
The transfer switch controls can either be enabled or disabled in software. This allows the controller to be used
only as an Engine Controller. Please note that disabling the transfer switch controls does not disable or turn off
the Exerciser Function, it only disables the controller from starting the generator on a loss of utility.
UTILITY SENSING
Operating & Installation Manual for the GSC200 Controller