Operation with the control module disabled:
Should the generator be started manually while the control module is disabled from the circuit,
the transfer switch will immediately switch to the generator source. There will be no time delays
prior to this transfer. The automatic transfer switch will be fully operational but with no time
delays with the control module disabled.
Servicing
When servicing the transfer switch, the control module cable should be disconnected at the
transfer switch to prevent starting of the engine while working on the equipment.
What the LED's look like
No LED's ON.
Low Oil, steady
Low Oil, flashing
High Temperature, steady
Over-crank, steady
Over-Speed, steady
Engine Running, steady
Engine Running, flashing
Low Oil steady while
Engine Running Flashing
Installation and User Manual for the ES53 Control Module
LED INDICATIONS
FRONT PANEL LED INDICATIONS
"Ready" unit waiting for start signal,
+12/24 VDC to Auto terminal.
"OFF", no +12/24 VDC to Auto terminal.
Low Oil Pressure Failure
Auxiliary Input Failure
Over-temperature Failure
Engine would not start after specified
Crank tries.
Speed Signal present above Over-Speed
setting
Engine Controller is in running mode of
operation.
Crank-rest period. Cranking will resume
soon.
Oil switch is not closed (miswired or not
Installed). Engine will crank when oil
Condition/Failure
switch verifies.