Section 4: Input and Output Data
November 2021
4.2.7

Status 3

Module number: 18
ID-byte: 50
Data format: 16-bit, error number
Table 10.
Parameter P15.7 can be used to set alternative output functions for Status 3.
4.2.8

Status 4

Module number: 19
ID-byte: 50
Data format: 16-bit (bit field)
Reserved for future use.
Structure:
Table 11.
Bit no.
0 and 1
2
3
4
5
6
7
8 and 9
10
11
12
13
14
15
Parameter P15.6 can be used to set alternative output functions for Status 2.
12
Installation, Operation and Maintenance Manual
Hex
(1 word AA / consistency 1 word)
Hex
Error Code
Meaning
3
Motor temperature warning
4
Motor temperature cut-out
5
Phase sequence error or phase loss
9
Error in the power supply or the frequency converter
11
Error in the failsafe unit (provided there is one)
17
Fault, displacement potentiometer
22
Fault, torque potentiometer
Hex
(1 word AA / consistency 1 word)
Hex
Function
Description
Bit1
0
Channel Activity
0
1
1
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Bit9
0
PVST Status
0
1
1
reserved
reserved
reserved
reserved
reserved
reserved
Bit0 Signal
0
Bus: Channel A active.
1
Bus: Channel B active.
0
Bus: Channel A and B active, main channel for inputs is channel A.
1
Bus: Channel A and B active, main channel for inputs is channel B.
Bit8 Signal
0
PVST functionality not activated or no PVST realised yet.
1
PVST active: There is a PVST active currently.
0
PVST OK: The last PVST was successful.
1
PVST Error: The last PVST was not successful.
VCIOM-15590-EN Rev. 0
Input and Output Data