Installation & Operation Manual
CO2 MONITOR & 12VDC
Primarily this is used to power the AGS CO2-X but can be used as a power output for external auxiliary
devices when there is power at the panel and can be used to create a relay switch with the BMS relay
output. Max output: 50mA. If no CO2 monitor or other device is connected, the panel will 'beep' upon
power up and the CO2 LED will flash 3 times to indicate that this terminal has been disabled.
Switch Settings – Auto Reset
When power is restored after the power cut/ loss, the panel has to be restarted
OFF
manually. (Default)
This will instruct the system to restart automatically when power is restored after
ON
power cut/loss.
Switch Settings – BMS Integration
The panel can be integrated with a BMS to make or break a circuit when the gas is either on or off,
(valve open or valve closed). This will tell the BMS whether power is being sent to the solenoid valve.
OFF
Signals the BMS when gas is on or gas is off. (Default)
Signals the BMS on a fault i.e. high gas levels detected, emergency shut-off
ON
activated etc.
Rev: 13
08-22