AGS Merlin 2000S Panduan Pengguna - Halaman 10

Jelajahi secara online atau unduh pdf Panduan Pengguna untuk Detektor Gas AGS Merlin 2000S. AGS Merlin 2000S 12 halaman. Gas proving and ventilation interlock system
Juga untuk AGS Merlin 2000S: Panduan Pemasangan & Pengoperasian (12 halaman), Panduan Pemasangan & Pengoperasian (12 halaman)

AGS Merlin 2000S Panduan Pengguna
Merlin 2000S
5

2000S Wiring Spec

1.
LINE VOLTAGE: Mains Input 110-120VAC. Single phase
2.
VALVE OUT: Gas Solenoid Valve Power Output, 110-120VAC. Max 3A
3.
SUPPLY FAN 1 and 2 external pressure differential switch or current switch. VOLT FREE INPUT
4.
EXTRACT FAN 1 and 2 external pressure differential switch or current switch. VOLT FREE INPUT
5.
BMS OUT contacts. Normally Closed, Common and Normally Open.
6.
PRESSURE SENSOR: Gas pressure transducer, power supply and returned signal (supplied).
7.
EM REMOTE: Remote EM Stop buttons and Fire Alarm input wired in series (purchased separately).
VOLT FREE INPUT
8.
GAS DETECTOR: power supply and VOLT FREE INPUT (purchased separately).
9.
FS1/2/3/4: Fan Switch output (purchased separately).
For wiring instruction see Fan Switch user manual.
10. CO2 MONITOR: (purchased separately). VOLT FREE INPUT
11. 12VDC: Permanent 12VDC output (Normally used to power a PM2 Current Monitor). 50A Max.
Rev: 06
05-19
User Guide
10