2000S Wiring Spec
1.
LINE VOLTAGE: Mains Input 110-120VAC. Single phase
2.
VALVE OUT: Gas Solenoid Valve Power Output, 110-120VAC. Max 3A
3.
SUPPLY FAN 1 and 2 external pressure differential switch or current switch. VOLT FREE INPUT
4.
EXTRACT FAN 1 and 2 external pressure differential switch or current switch. VOLT FREE INPUT
5.
BMS OUT contacts. Normally Closed, Common and Normally Open.
6.
PRESSURE SENSOR: Gas pressure transducer, power supply and returned signal (supplied).
7.
EM REMOTE: Remote EM Stop buttons and Fire Alarm input wired in series (purchased separately).
VOLT FREE INPUT
8.
GAS DETECTOR: power supply and VOLT FREE INPUT (purchased separately).
9.
FS1/2/3/4: Fan Switch output (purchased separately).
For wiring instruction see Fan Switch user manual.
10. CO2 MONITOR: (purchased separately). VOLT FREE INPUT
11. 12VDC: Permanent 12VDC output (Normally used to power a PM2 Current Monitor). 50A Max.
Rev: 06
05-19
User Guide