3
OPERATION
How to turn the system on and off
1)
Turn off all open appliances.
2)
Turn the key switch to on position.
3)
To turn the system off, turn the key switch to off position.
Panel LED Status
POWER
When the system is connected to mains supply, the Red LED of the AGS Logo located in
the bottom right corner of the panel will illuminate.
When no power is present, this LED will not light up.
RED = OK
OFF = No power to 1000S, a loose wire/ribbon connection or the fuse may not be intact.
GAS ON
When the key switch is turned on, the Merlin 1000S will check the installation for gas leaks.
If gas proving is successful, the gas valve will open and the GAS ON LED will illuminate.
GREEN = Gas On
OFF = Gas Off
TESTING
This LED will illuminate GREEN for approximately 30 seconds when the panel is checking the
integrity of the gas installation upon start up.
GREEN = proving the gas line, do NOT operate any appliances.
TEST FAIL
Under normal working conditions this LED is off.
When the panel detects a gas leak on start-up, the LED will illuminate and the gas valve
will remain closed.
OFF = OK
AMBER = Gas proving failed
PRESSURE LOW
Under normal working conditions the LED is off.
The LED will illuminate when the pressure of gas supply drops below 0.17psi for 10 seconds
and the gas valve will close.
OFF = OK
AMBER = Gas supply pressure low.
TIMEOUT
Under normal working conditions this LED is off. This LED will illuminate upon auto-shut down
OFF = OK
AMBER = auto-shut down
Rev: 04 Date: 15-08-18
User & Installation Manual
6