AGS Merlin 1000S Panduan Pengguna & Instalasi - Halaman 4

Jelajahi secara online atau unduh pdf Panduan Pengguna & Instalasi untuk Peralatan Laboratorium AGS Merlin 1000S. AGS Merlin 1000S 10 halaman. Gas utility isolation controller
Juga untuk AGS Merlin 1000S: Panduan Pemasangan, Pengoperasian, dan Pemeliharaan (10 halaman), Panduan Pemasangan & Pengoperasian (12 halaman), Panduan Pemasangan & Pengoperasian (16 halaman)

AGS Merlin 1000S Panduan Pengguna & Instalasi
Merlin 1000S
Gas Utility Controller
(4)
[PRESSURE SENSOR]

Gas Pressure Transducer

The terminals marked pressure sensor "+ - IN ".These wire to the gas pressure transducer
which is screwed into the downstream port on the gas solenoid valve (see wiring below).
ENSURE THE TRANSDUCER IS CONNECTED TO THE DOWNSTREAM PORT.
Operating Pressure = 0.17psi min - 1.45psi max
(5)
[EM REMOTE]

Remote Emergency Shut Off Buttons

These connections are linked out as a factory setting. (fig1)
Remote emergency shut-off buttons should be volt free and
wired to the Merlin panel using a Plenum Security Cable. White,
18/2 (18AWG 2 Conductor), stranded, CMP or similar.
(6)
[GAS DETECTOR]

Gas Detectors

These terminals are [+ -] and [
These can be wired to various Merlin gas detectors.
For multiple detector wiring consult the gas detector manual (see example wiring below).
If no detector is being used leave the link in [
Rev: 04 Date: 15-08-18
] and should be volt free dry contact connections.
] (fig2)
User & Installation Manual
fig1
fig2
4