Maintronic DASPip UP Panduan Cepat - Halaman 3
Jelajahi secara online atau unduh pdf Panduan Cepat untuk Pengontrol Maintronic DASPip UP. Maintronic DASPip UP 6 halaman. Power pwm actuator 1ch
Connection to dimmer with PWM input
3. Connections
Screw terminal for 0.2 ... 2.5 mm² stranded wire
or 0.2 ... 4 mm² single wire
DASPip INS
N - Neutral conductor
N - Neutral conductor
L - Mains 230V AC
L´ - Load output (switched phase L´)
D1 - DALI data (alt. tastDIM)
D2 - DALI data (alt. tastDIM)
DIMM PWM + (brown wire)
DIMM PWM - (blue wire)
DASP
iP
INS
tc
DALI 1CH
POWER PWM
ACTUATOR
L
N
120-240 V
tast
DIM
ta 0-50C°
DALI
N
N
L L´
D1 D2
-X1
1 2 3 4
5 6
7
8
7
DASPip UP
1
N - Neutral conductor
2
N - Neutral conductor
3
L - Mains 230V AC
4
L - Mains 230V AC
5
L - Mains 230V AC
6
L´ - Load output (switched phase L´)
7
D1 - DALI data (alt. tastDIM)
8
D2 - DALI data (alt. tastDIM)
9
DIMM PWM -
10
DIMM PWM +
8
4. DALI general
DALI (Digital Addressable Lighting Interface) is a standardized
digital communication interface in the field of building auto-
mation.
4.1 DALI note
The DALI signal is not SELV (safety extra-low voltage), the ins-
tallation instructions for mains voltage apply.
The maximum cable length of the DALI control cable must not
exceed 300m (with 1.5mm² cable cross-section) or 2V voltage
drop.
4.2 Groups and Scenes
In each DALI circle 16 groups can be formed, with each 16
scenes. A scene includes the brightness value of a short
address.
4.3 DALI device-specific
The device search assigns a DALI short address to the DASPip
INS. Please note the operating instructions for your DALI con-
troller or gateway.
The module works accordingly to the following regulations:
IEC 62386-101, General requirements; System
IEC 62386-102, General requirements; Control gear
IEC 62386-207, Particular requirements for control gear -
LED-modules (device type 6)
9